PGFS-73105
Ground Fault Circuit Interrupter-Permanent Splice ...
DESCRIPTION
The LineGard™ 30 Amp Permanent Series is an industrial grade ground fault interrupter device designed and manufactured by North Shore Safety, Ltd., a leader in innovated safety products. The unique design offers the flexibility of splicing in protection of a GFCI anywhere within the length of the circuit run, making it ideal for both new and existing applications. Unlike breaker style GFCI’s which have limitations of circuit length from the service panel, the PFGS series can be integrated directly into a circuit or paired in tandem with an approved receptacle and enclosure. Rated Current Up to 30 Amps or rating of wiring device and/or cable Horse Power 1HP@120 VAC, 3HP@240 VAC Trip Level 5mA +/–1mA Operating Frequency 60 Hz Reset Type1 Automatic or Manual Phase Dual voltage and 3 phase Response Time 25mS max Operating Temperature –35°C to 66°C Operating Voltage Range 85% to 110% of rated VAC Let-Go Voltage 60% of supply voltage Open Neutral Protection Trips upon loss of neutral
Search Keywords: PGFS73105
SPECIFICATIONS
FREQUENTLY ASKED QUESTIONS
Is PGFS-73105 discontinued?
Yes, PGFS-73105 from Sensata / Airpax is discontinued. Master Electronics is an authorized distributor and may have remaining stock or a recommended replacement for it.
Is PGFS-73105 RoHS compliant?
Yes, PGFS-73105 is RoHS compliant.
What is the lead time for PGFS-73105?
The standard lead time for PGFS-73105 is approximately 2 weeks. In-stock quantities ship from Master Electronics.